Our Products - TStats-HStats-PStats

DBET/DBMT

DBETDownload PDF

Functions

Room temperature control in:
● single or multi-stage heating systems;
● single or multi-stage cooling systems;
● single or two-stage heating and cooling systems with dead zone.
Models with set point adjustment by knob upper or under the cover and range reset.

Applications

Well-suited for heating, cooling and air conditioning systems in dusty, damp and strong polluted areas: industrial areas, commercial buildings, storage room, garages, machine rooms, factories, greenhouses and agricultural installations.

Electrical Wirings

Heating
Connect red (common) to blue terminal, as shown in fig. 2; while rising of the temperature, the conctacts open, in sequence, the stages from the last to the first.

Cooling
Connect red (common) to white terminal; while droping of the temperature, the conctacts open in sequence the stages from the first to the last. The respective free contact closes simultaneously (signal contact).

 

Range Type Stages Diff. in stage Diff. betw stages Max bulb temp. Special Ver.
-30...+30 DBET-22 1 2.... 15   60 U
-30...+30 DBET-23 1 1   60 U
-30...+30 DBET-22/2 2 1 2... 10 60 U
-30...+30 DBET-412 4 1 1 60 (*)
0...+60 DBET-26 1 2.... 15   75 U
0...+60 DBET-27 1 1   75 U
0...+60 DBET-26/2 2 1 2... 10 75 U
0...+60 DBET-413 4 1 1 5 (*)

Dimensions

Technical Features

Sensitive elem. liquid-filled coiled copper bulb
Contacts dust-tight microswitches with switching contacts (heat/cool)
Switch capacity 15 (8) A, 24...250 Vac
Differentials fixed or adjustable (see schedule)
Working temperature -35...+65 °C
Storage -20...+70 °C
Housing DBET: Byblend base, ABS cover
DBMT: ABS Makrolon
Size DBET: 108 x 70 x 72 mm
DBMT: 200 x 120 x 74 mm
Protection IP65, class I