Velocity Settings
There are two Velocity adjustments. The first is Maximum, which has a range of 0–15 m/s. Typical settings are around 5 – 8 m/s. The second is Minimum, which is set as a percentage of Max. Typical settings are 50 – 60%.
Motor Travel
The motor travel can be adjusted in the clockwise direction over the range of 30 – 90 degrees.
Dip Switch Settings
There are two Dip Switches. The first is for Motor direction, either CW or CCW. The second is for Motor direction on power fail, provided a Power Fail Module is fitted.
BACnet Comms Termination
A terminating resistor of 120 ohms should be installed at the end of the RS485 transmission line. With the VM2912, this resistor is on-board and it is only necessary to install a shorting plug on the BACnet comms terminating link.
Duct Sensor
For applications where hot or cold air is supplied to the VAV, then the VAV Controller must be able change its control function from direct acting to reverse acting. This can be detected by a Duct Probe mounted upstream of the VAV. This Probe is plugged into a two-pin header, located on the left-hand side of the terminal strip.
Terminal Connections