| FUNCTION DEFAULT |
DECIMAL POINT OFF ACTIVE |
DECIMAL POINT FLASHING |
| 1 |
Sensor 0 (Internal) |
Sensor 1 (External) |
| 2 |
Sensor 0 (Internal) |
Sensor 0 (Internal) Z1 & Sensor 1 (External) Z2 |
| 3 |
Sensor 0 (Internal) |
Sensor 1 (External) Z1 & Sensor 2 (External) Z2 |
| 4 |
Sensor 0 (Internal) |
Sensor 3 (Relay Board) |
| 7 |
Zone Control Enabled |
Zone Control Disabled – Function 1 & 4 only |
| 8 |
Zone 1 or Zone 2 or Both |
Zone 1 or Zone 2 Only (F7 Enabled) |
| 10 |
Override Input Disabled |
Override Input Enabled |
| 11 |
Room Temp & Setpoint |
16 – 30˚C Display Setpoint Only 16 – 30˚C |
| 12 |
Room Temp & Setpoint |
16 – 30˚C Room Temp & Setpoint 20 – 26˚C |
| 13 |
Room Temp & Setpoint |
16 – 30˚C Display Setpoint Only 1 – 15 (19-26˚C) |
| 17 |
Fan – Auto (Cycles with Temp) |
Fan – Continuous |
| 18 |
Fan – 3 Speed |
Fan – 1 Speed |
| 22 |
Reverse Cycle – 1H/1C |
On/Off Cool & On/Off Heat |
| 23 |
Reverse Cycle – 1H/1C |
On/Off Cool & Electric Reheat |
| 24 |
Reverse Cycle – 1H/1C |
On/Off Cool & Time Prop Electric Reheat |
| 25 |
Reverse Cycle – 1H/1C |
Thermal Valve Cool (Prop) & Electric Reheat |
| 26 |
Reverse Cycle – 1H/1C |
Thermal Valve Cool & Time Prop Electric Reheat |
| 27 |
Reverse Cycle – 1H/1C |
Thermal Valve Cool & Thermal Valve Heat (Prop) |
| 28 |
Reverse Cycle – 1H/1C |
Two Cool / Two Heat (4 Stage) |
| 29 |
Reverse Cycle – 1H/1C |
Two Cool / Two Heat (4 Stage) Reverse Cycle |
| 30 |
Auto C/O for 2 Pipe Systems Disabled |
Auto C/O for 2 Pipe Systems – Sensor 3 & Cool 1 |
| 31 |
Thermal Valve Non-Linear PWM |
Rate Thermal Valve Linear PWM Rate |
| 34 |
Reversing Valve – Heat |
Reversing Valve – Cool |
| 35 |
Auto Changeover – Heat/Cool |
Cooling Only |
| 36 |
Auto Changeover – Heat/Cool |
Heating Only |
| 40 |
Filter Timer 200 Hrs – Disabled |
Filter Timer 200 Hrs – Enabled |
| 41 |
Ventilation Timer – Disabled |
Ventilation Timer – Enabled (12Hrs / 30Mins) |
| 42 |
Cond Water Pump – Disabled |
Cond Water Pump Relay & Interlock Enabled |
| 43 |
C W Pump Interlock Timeout-10sec |
Cond Water Pump Interlock Timeout – 0 secs |
| 46 |
Lo Limit Control Disabled Lo Limit |
Cooling – Sensor 3 On 9C/Off 4C F22 only |
| 48 |
Start to Start Comp Delay – 6 mins |
Stop to Start Compressor Delay – 30 secs |