The HC2004 can be used with any 4 - 20 mA Humidity Sensor, two or three wire connection. The HC2004 has a 12VDC supply available from terminal 1 for loop powered devices. If a higher voltage is required, then an external power supply is connected to the sensor (+) and terminal 3 (signal ground). The sensor output (-) is connected to terminal 2 (input). For three wire devices, connect to terminals 1, 2 andamp; 3. The zero and span potentiometers can be used to adjust the 4 - 20 mA signal to display a range from 0 to 100. Dip switches 1 andamp; 2 are used to set the decimal points. They are not required in this instance. Dip switch 3 is not used.

The HC2004 generates 2 voltage signals, D/A direct acting and R/A reverse acting. Each is independently adjustable. These 0 - 10vdc signals are proportional to the deviation of the input humidity to the setpoint. E.G. With a P-Band setting of 5%, this will give a 0 - 10vdc output with a 5%RH change at the sensor. With a P-Band setting of 20%, this will give a 0 - 10vdc output with a 20%RH change at the sensor.
Sensor Inputs
4-20mA loop powered transducer. Connect between terminals 1 and 2. If transducer is externally powered, then connect between terminals 2 and 3.
Common Signal Ground
All signal inputs and control voltage outputs are referenced to this point. In multiple control configurations, #3 must be commoned.
Remote Set Point
If a remote setpoint is required, it is wired across terminals 3 and 4. The standard humidity setpoint has a range of 40-90% RH combined with a temperature setpoint of 10-35°C. Other ranges by special order. The external remote setpoint is only operational when the remote setpoint switch on the front panel is switched to remote setpoint.
Set Point Change
If a remote setpoint is required, it is wired across terminals 3 and 4. The standard humidity setpoint has a range of 40-90% RH combined with a temperature setpoint of 10-35°C. Other ranges by special order. The external remote setpoint is only operational when the remote setpoint switch on the front panel is switched to remote setpoint.
240VAC/24VAC
All System 2000 Controllers have internal mains transformer isolation. Active supply is via terminals 17 and 18. Terminals 19 to 32 are relay connections.Relays are rated 2.5 amps at 240VAC.
D/A and R/A 0-10VDC Output
When switched to the D/A or R/A position, these output voltages are the same as shown on the front panel digital display. These voltages are generated by the HC2004 in response to movement away from the setpoint of the measured variable and are the voltage ramps used to switch the internal relays. Used for analog output for external equipment control.
D/A and R/A High Select
These terminals are used for high selecting on multiple control hookups. Voltages are the same as for 0-10 output terminals. Diode protected to prevent voltage feeding back into the controller.
Relay 3 and 4 Input
When it is desired to operate a relay from an external signal then the dip switch settings on the appropriate relay card are switched to external signal. These external signals are connected to terminal 11 for relay 3 and terminal 12 for relay 4.
0V to +10V DC
This terminal output is a direct output voltage of the input signal. In the HC2004 it represents 0% RH to 100% RH. Commonly used to interface with a DDC or BMS system.NOTE: If there is a sensor fault and the Controller shuts down, this voltage drops to -15VDC allowing for an external fault indicator to be incorporated.