Digital Display & Display Selector Switch
The Display Selector Switch has five positions:
1 TEMP °C Displays the sensor temperature with 0.1°C resolution from -40°C to +100°C.
2 INT S.P. Displays the INTERNAL SETPOINT to which the controller is working from -40°Cto100°C.
3 EXT S.P. Displays the remote setpoint when the external setpoint is installed and the INT EXT switch is set to EXT; standard remote setpoints are 10 - 35°C and 18 - 28°C.
4 D/A Displays the 0-10VDC signal generated when the temperature is ABOVE the setpoint selected.
5 R/A Displays the 0-10VDC signal generated when the temperature is BELOW the setpoint selected.
Relay Setpoints & LED Display
The operation of the relay stages in the system are indicated by the respective LED’s and controlled by the potentiometers immediately below the digital display.The pull in volts is set by the left potentiometer and the differential by the right potentiometer. When the relay is energised the LED is illuminated. The zero volts drop out feature prevents any relay from locking on if the differential voltage is set higher than the pull in volts.The internal circuitry will drop out the relay at 100mV. (The settings on the differential are in volts not in percentage of pull in volts.)
Sensor Fault & Setpoint Selection & Adjustment
At the lower left is the sensor fault light to indicate when a fault is detected and shutdown is effected. A setpoint adjustment screw is located to the right of the sensor LED and a switch to select internal or external setpoint is located below.

Sensor Inputs
There are several inputs available for the TC2000:
1.THERMISTOR An NTC thermistor (internally linearised) supplying the -40°C to +100°C range. Available as switchplate mounted, duct or encapsulated formats. Accuracy to +/-0.2°C.
2. 4 - 20mA. Any temperature sensor that has a 4 - 20mA output. E.G. Thermocouple, RTD, etc.
Common Signal Ground
All signal inputs and control voltage outputs are referenced to this point. In multiple control configurations, #3 must be commoned.
Remote Setpoint
If a remote setpoint is required, it is wired across terminals 3 & 4. The common temperature setpoint has a range of 18 - 28°C. Other ranges are 10 - 35°C and 0 - 50°C.
Setpoint Change
This terminal accepts a +10v to - 10v signal to vary the setpoint up and down ±20°C. Commonly this signal would be derived from a DDC or BMS system, or another controller. The altered setpoint is displayed on the EXT S.P. position on the front panel. The INT EXT switch is set to INT.
-4v to +10v DC
This terminal output is a direct output voltage representation of the input signal. In the TC2000 it represents -40°C to +100°C. Commonly used to interface with a DDC or BMS system. NOTE: If there is a sensor fault and the controller shuts down, this voltage drops to -15VDC allowing for an external fault indicator to be incorporated.
D/A & R/A 0-10VDC Output
When switched to the D/A or R/A position, these outputs voltages are the same as shown on the front panel digital display. These voltages are generated by the TC2000 in response to movement away from the setpoint of the measured variable(e.g. temperature, humidity, etc.) and are the voltage ramps used to switch the internal relays. Used for analog output for externalequipment control.
D/A & R/A High Select
These terminals are used for high selecting on multiple control hookups. Voltages are the same as for 0-10 output terminals . Diode protected to prevent voltage feeding back into the controller.
Relay 3 & 4 Input
When it is desired to operate a relay from an external signal then the dip switch settings on the relay card are switched to external signal. These external signals are connected to terminal 11 for relay 3 and terminal 12 for relay 4.
240VAC/24VAC
All System 2000 Controllers have internal mains transformer isolation. Active supply is via terminals 17 & 18. Terminals 19 to 32 are relay connections.Relays are rated 2.5 amps at 240VAC.