The TR2104, TR2114 and TR4114 units combine a remote setpoint with a temperature sensor. The setpoint range is 18-28°C. This provides the convenience of reduced wiring, and having the setpoint at a suitable location. Both units feature our standard thermistor temperature sensor mounted in specially designed vented enclosure.
The TR2104 has a concealed setpoint, which becomes accessible when the surround is removed. A small screwdriver is required to adjust the setpoint. The TR2114 AND TR4114 have an exposed setpoint with knob located in the centre of the front panel which provides an easy to adjustment for the user. The TR4114 has a 4000 ohm temperature sensor for use in averaging applications.
Sensor - TR2104 & TR2114 NTC Thermistor, 2 K ohms @ 25° C
Sensor - TR4114 NTC Thermistor, 4 K ohms @ 25° C
Sensor accuracy +/- 0.3°C over 0 - 70°C
Setpoint Range TR 2104, TR2114 and TR4114 18 - 28°C
Setpoint Resistance TR 2104, TR2114 and TR4114 3.6 K to 5.6 K ohms
Voltage output with 0.5 mA constant current source 1.8 to 2.8 vdc
Maximum connection cable 500 m with 1.00 mm2Cu. Use shielded cable if run with power cables. Maximum connection length reduced to 250m. Suitable for all Regulator Controllers except ET4 and SYSTEM 80.