The Configuration Menu is as set out below:
EXIT
SETPOINT RANGE
SYSTEM TIMER
SENSOR DISABLE
SETPOINT RES
STANDALONE
EXIT
Setpoint Range
TR3840 Smart Sensor – Temp Only
To change the Setpoint Range push and hold the SEL button for 10 seconds.
SETPOINT RANGE will appear.
Push SEL and 20-25C will appear or whatever range may have been previously set.
The Lower Setpoint will be 20C or the last value entered.
Raise or lower this to the desired value.
Push the SEL button. The Upper Setpoint can now be adjusted to the desired value.
Press SEL and the display will return to the main screen.
TR3740 Smart Sensor – Temp & Humid
Pressing the SEL button will alternate between Temp & Humid Setpoints.
Select Temp SP, press and hold SEL for 10 seconds and adjust as above.
For Humidity Setpoint Range adjustment, select Humid SP, press and hold SEL for 10 seconds and adjust as above. The values will be %RH not degrees C.
Default range is 50-60%RH
System Timer
This function is used to set a run time for the A/C system whenever the TC5042 is set for FAN CONTROL.
For example, if set for 2 hours and the On/Off button is pushed, the system will run for 2 hours and turn off.
If the system is running, pressing the On/Off button will still turn the system off.
Press SEL for 10 seconds to enter the main menu page.
Scroll down to System Timer.
Press SEL and HOURS will appear.
Scroll up or down (if previously set) to adjust the run time in 0.5hr increments. Max 12 hours.
Press SEL and the display will return to the main screen.
Sensor Disable
This function is used to disable the internal sensor if the TR3840 is being used as a Remote Setpoint and/or an On/Off control.
Press SEL for 10 seconds and scroll down to SENSOR DISABLE.
Press SEL and SENSOR DISABLE NO and YES will be displayed.
Scroll down to YES, press SEL, the sensor is now disabled and the display will return to the main screen.
Setpoint Res (Resolution)
This function is for changing the Setpoint Resolution from 0.5C to 0.1C.
Press SEL for 10 seconds and scroll down to SENSOR RES.
Press SEL and 0.5C and 0.1C will be displayed.
Scroll down to 0.1C.
Press SEL and the display will return to the main screen.
Standalone
The Standalone mode will allow the TR3840 or TR3740 Smart Sensors to operate as a remote Temperature and/or Humidity display.
Connect the Smart Sensor to an external power supply, 8-24VDC.
After 10 seconds, an ERROR 1 will be displayed, indicating a communications error.
Press SEL button and STANDALONE NO or YES will be displayed.
Scroll down to YES.
Press SEL and the display will return to the main menu.